Key Capabilities
Operating Modes
Auto-Start (A/S) Mode
In Auto-Start Mode, the M300DP enables unattended engine operation based on discrete input triggers. Typical functions include:
- Engine start and stop sequencing
- Programmable start delays
- Throttle profile control during startup and shutdown
- Ramping through Speed 1, Speed 2, and final engine speed
Auto-Start Mode is commonly used in applications such as tank level control, where a float switch triggers engine start and stop events.
Expansion I/O Mode
In Expansion I/O Mode, auto-start functionality is disabled and the M300DP operates strictly as an I/O expansion module. In this mode, the module provides:
- Two additional analog inputs
- Two digital inputs for remote speed selection or control logic
Inputs & Outputs Overview
Analog Inputs
- 2 Analog Inputs (AI1, AI2) configurable for:
- Fuel level senders (US 240–33 Ω and Euro 10–180 Ω)
- Oil pressure senders (5 bar and 10 bar ranges)
- Water level sensing (US 240–33 Ω and Euro 10–180 Ω)
Analog inputs are available in all operating modes.
Digital Inputs
- 2 Digital Inputs (DI1, DI2) configurable for:
- Start
- Stop
- Start/Stop
- Start Inhibit
- Speed 1 or Speed 2 selection
Input active state (normally open or normally closed) and timing delays are user configurable.
Outputs
- Starter control output
- Ignition control output
- Alarm output (low-side switch closure to ground)
Engine Speed & Throttle Control
The M300DP provides programmable engine speed control through discrete input selection and configurable throttle profiles.
- Up to three programmable engine speed setpoints (engine-dependent)
- Configurable ramp-up and ramp-down times
- Controlled acceleration and deceleration to reduce mechanical stress
Throttle profiles allow the engine to transition smoothly between idle, intermediate speeds, and final operating RPM.
Integration & Compatibility
- Requires an MBW engine controller
- Not intended for standalone engine control
- Configuration performed through MBW controller interface
- Designed for integration in pump, standby, and industrial systems
The M300DP Auto-Start Module is designed to operate in conjunction with MBW engine controllers and control panels. It relies on the primary MBW controller for engine control logic, operator display, configuration, and alarm handling.
The M300DP adds auto-start functionality, remote speed control, and additional I/O capability, but it does not function as a standalone engine controller and is not intended to operate independently of an MBW control system.
When properly integrated, the M300DP communicates with an MBW controller to execute start/stop sequences, throttle profiles, and speed commands based on configured inputs and application requirements.
Typical Applications
- Industrial pump systems
- Standby and backup equipment
- Automated engine start applications
- Retrofit installations requiring auto-start capability
Environmental & Electrical Summary
|
Parameter |
Specification |
|---|---|
|
Operating Voltage |
9–32 VDC |
|
Operating Temperature |
−30 °C to +70 °C |
|
Storage Temperature |
−40 °C to +80 °C |
|
Communication Interface |
SAE J1939 CAN 2.0B |
|
Housing |
Sealed, potted electronics module |
|
Reverse Polarity Protection |
Yes |
Configuration & Installation Notes
- Configuration is performed through the MBW control panel interface
- Password-protected setup menus prevent unintended changes
- Requires field wiring for analog and digital inputs
- Refer to the M300DP Installation / User Manual for detailed wiring and setup instructions